Why bother purging with nitrogen between units? Just purge the refrigerant that is in them out and go.
Replies 8Shortcuts seldom work.
Replies 3The DRSA series are the MOST DURABLE set of gauges you can buy. Mine have been in WI Freezers at -15, on rooftops at over 100, dropped, dunked in water, splashed with e...
Replies 8All cylinders have relief devices. They won't explode.
Replies 5With a receiver system (assumption since you mentioned sightglass) you would need a massive overcharge to adversely affect head pressure. Look to a dirty condenser or some oth...
Replies 17Try taking a logical, methodical approach to troubleshooting rather than jumping around. Check the things I told you to check, it will give you a much better idea as to what is...
Replies 17I am not a fan of troubleshooting by replacing parts.
Replies 17Since there is a HUGE difference in capacity between the two refrigerants, I'm going to say that it won't work well. The oil would be a non-issue as POE is compatible with all...
Replies 14What sort of reach-in has a target of 50-55 degrees? About the only thing I can think of would be for wine chilling application.... Depending on what type of temperature con...
Replies 17What controls the system? Low pressure control? Coil sensing t-stat? Air sensing t-stat with defrost timer?
Replies 17Damn, this site isn't even that busy. How'd he get banned so quick?
Replies 4R-410 is generally not used as a medium or low temperature refrigerant. It would be MUCH more common to see R404a in an application like you are describing. If it is environ...